    Calculates locally in your browser · arc flash incident energy
    Electrical / safety

    Arc flash incident energy

    The calculation that decides what an electrician wears when they open a panel. It is an empirical regression on laboratory arcs, and it is the reason NFPA 70E exists in its current form: before it, incident energy was estimated from a table of fault current and time, and people were burned.

    VerdictHigh energyDistance exponent1.64Clearing time100 ms
    Incident energy
    20.67 cal/cm²
    at 455 mm working distance
    Arc flash boundary
    2.58 m
    where the energy falls to 1.2 cal/cm²
    Arcing current
    14.34 kA
    57% of the bolted fault
    PPE required
    Category 3
    category 3
    Incident energy working
    The regression first, then the geometry and the time.
    20.7 cal/cm²
    Incident energy working
    QuantityValueNote
    System voltage480 Vlow voltage, 2002 model
    Bolted fault current25.0 kAfrom the short-circuit study
    Electrode gap25 mmIEEE 1584 Table 4
    ConfigurationIn a boxK = −0.097, K1 = −0.555
    GroundingSolidly groundedK2 = −0.113
    Arcing current14.34 kAthe regression output
    Normalised energy4.07 cal/cm²at 610 mm, 0.2 s
    Working distance455 mm
    Distance exponent x1.6411.641 in a box below 1 kV
    Clearing time0.100 sprotection operating time
    Incident energy20.67 cal/cm²86.5 J/cm²
    Arc flash boundary2579 mm2.58 m
    PPE category3Category 3
    Time for 8 cal/cm²39 msthe protection target

    The clearing time is the variable the electrical engineer actually controls. Incident energy is linear in it, so halving the protection time halves the hazard — which is why arc-rated switchgear and faster relays matter more than warning labels.

    Inspect the model
    Choose a quick result view, a scaled comparison, or the complete diagnostic set.
    Incident energy against fault current
    Rises steeply and then flattens: the arc current saturates as the fault current grows.
    Incident energy against fault current0.00011.1922.3833.5744.7755.965kA5kA10kA10kA15kA15kA20kA20kA25kA25kA35kA35kA50kA50kA65kA65kAcal/cm²
    Incident energy against working distance
    Falls with the distance exponent — 1.641 in a box, 2.0 in open air.
    Incident energy against working distance0.0008.9317.8626.7835.7144.643053054554556106109109101220122018301830cal/cm²
    Canonical equations
    The exact relationships implemented by this engine.

    lg Ia = K + 0.662 lg Ibf + 0.0966V + 0.000526G + 0.5588V lg Ibf − 0.00304G lg Ibf · V in kV, G in mm.

    lg En = K1 + K2 + 1.081 lg Ia + 0.0011G · At 610 mm and 0.2 s.

    E = 4.184 Cf En (t/0.2)(610^x/D^x) · Cf = 1.5 below 1 kV.

    DB = [4.184 Cf En (t/0.2) 610^x / 1.2]^(1/x) · Where E = 1.2 cal/cm².

    engineering methodology

    A clear path from inputs to results.

    The calculation that decides what an electrician wears when they open a panel. It is an empirical regression on laboratory arcs, and it is the reason NFPA 70E exists in its current form: before it, incident energy was estimated from a table of fault current and time, and people were burned.

    Step-by-step methodWorked exampleAssumptions explained

    How to use

    1. Enter the system voltage and the bolted fault current.
    2. Set the electrode gap and the working distance.
    3. Enter the clearing time and whether the equipment is enclosed.
    4. Read the incident energy, the arc flash boundary and the PPE category.

    The formula

    E=4.184 CfEn(t0.2)(610D)xE = 4.184\,C_f E_n \left(\frac{t}{0.2}\right)\left(\frac{610}{D}\right)^{x}

    Reference: IEEE 1584-2002, Guide for Performing Arc-Flash Hazard Calculations; NFPA 70E for the PPE categories.

    Worked example

    A 480 V panel with 25 kA of fault current

    Inputs
    • 480 V, 25 kA bolted fault, 25 mm gap.
    • 455 mm working distance, 100 ms clearing, in an enclosure, solidly grounded.
    Calculation path
    1. 1

      The arcing current regresses to 14.34 kA, about 57% of the bolted fault.

    2. 2

      The normalised energy at 610 mm and 0.2 s is 43.4 cal/cm².

    3. 3

      Scaling to the 455 mm working distance with x = 1.641 and the 100 ms clearing time gives 20.67 cal/cm².

    4. 4

      That is 87 J/cm², which puts the task in PPE Category 3.

    5. 5

      The arc flash boundary, where the energy falls to 1.2 cal/cm², is 2.58 m from the equipment.

    Result

    14.34 kA arcing · 20.67 cal/cm² · 2.58 m boundary · Category 3.

    Interpreting the result

    Clearing time is the variable the electrical engineer actually controls, and incident energy is linear in it. Halving the protection time halves the hazard, which is why arc-rated switchgear and faster relays matter more than warning labels — and why the calculation is really a protection-coordination study in disguise.

    Assumptions & limitations

    • The IEEE 1584-2002 empirical equations, valid from 208 V to 15 kV.
    • A three-phase arc in a box or in open air, with the standard electrode gap.
    • The clearing time is the protection operating time, not the arcing duration.
    • No current-limiting devices and no arc-rated mitigation.

    Frequently asked questions

    Why use the 2002 model rather than 2018?

    Because it is what the NFPA 70E tables and most installed software still use, and because the two differ by 30% or more on some configurations — a live argument in the industry.

    What is a Category 3 task?

    PPE rated for 8 to 25 cal/cm²: an arc-rated flash suit over natural-fibre clothing. Above 40 cal/cm² no PPE is considered adequate and the work should be de-energised.

    What is the arc flash boundary?

    The distance at which the incident energy falls to 1.2 cal/cm², the threshold for a second-degree burn. Anyone inside it needs arc-rated PPE.

    Does the arcing current always equal the bolted fault?

    No, and that is the point of the regression. An arc has impedance, so the arcing current is typically 50–60% of the bolted value — which changes the energy substantially.

    Methodology last reviewed 2026-10-22. Results are informational and not financial or engineering advice — see our disclaimer.