    Calculates locally in your browser · battery runtime
    Electrical / standby power

    Battery runtime and UPS sizing

    A battery rated at 100 Ah does not deliver 100 Ah to a heavy load. The rated figure is measured over twenty hours, and the capacity you actually get falls as the current rises — which is why a runtime estimate that ignores Peukert can be out by a factor of two.

    Peukert loss36%C-rate0.46CAgainst nominal64%
    Runtime
    1.11 h
    66 minutes to 80% depth
    Usable energy
    615 Wh
    of 1200 Wh nominal
    DC current
    46.3 A
    556 W drawn at 12 V
    Recharge
    5.0 h
    at 20.0 A, including the absorption taper
    Runtime working
    The rated capacity is a twenty-hour figure; at a heavy load you get less of it.
    1.1 h
    Runtime working
    QuantityValueNote
    Battery100 Ah at 12 V1200 Wh nominal
    Load500 Wat the inverter output
    Inverter efficiency90.0%556 W drawn from the battery
    DC current46.3 A0.46C
    Twenty-hour current5.00 Athe rate the capacity is rated at
    Peukert exponent1.201.0 ideal, 1.15–1.3 lead-acid
    Capacity at this rate64.1 Ah36% below rated
    Depth of discharge80%how far you are willing to run it down
    Temperature derating100%capacity falls in the cold
    Age derating100%end-of-life capacity as a fraction of new
    Usable capacity51.3 Ahafter every derating
    Runtime1.11 husable capacity divided by current
    Usable energy615 What the nominal voltage
    Inverter loss over the run62 Whheat in the inverter
    Recharge time5.0 hat 20.0 A

    The nominal runtime ignores Peukert entirely, which is why the two columns differ. On a heavy load the real figure can be half the nominal one — the single largest source of error in small UPS sizing.

    Inspect the model
    Choose a quick result view, a scaled comparison, or the complete diagnostic set.
    Runtime against load
    Falls faster than 1/load, because the capacity itself shrinks as the current rises.
    Runtime against load0.0003.877.7411.6115.4819.355050100100200200300300500500750750100010001500150020002000Hours
    Nominal against real runtime
    The gap is Peukert, then temperature and age — all of them real, none of them in the brochure.
    Nominal against real runtime0.0000.4080.8161.221.632.041.73NominalNominal1.11After PeukertAfter Peukert1.11UsableUsableHours
    Canonical equations
    The exact relationships implemented by this engine.

    t = C_usable / I · Current is the DC load divided by the inverter efficiency.

    C = C₂₀ (C₂₀ / (I·20))^(k−1) · Referred to the twenty-hour rate.

    C·DoD·f_temp·f_age · Every derating multiplies.

    t = C·DoD·1.25 / I_charger · The 1.25 covers charging losses and the taper.

    engineering methodology

    A clear path from inputs to results.

    A battery rated at 100 Ah does not deliver 100 Ah to a heavy load. The rated figure is measured over twenty hours, and the capacity you actually get falls as the current rises — which is why a runtime estimate that ignores Peukert can be out by a factor of two.

    Step-by-step methodWorked exampleAssumptions explained

    How to use

    1. Enter the rated capacity and the nominal voltage.
    2. Set the load at the inverter output and the inverter efficiency.
    3. Choose the depth of discharge you are willing to run to.
    4. Apply the temperature and age derating, and set the Peukert exponent.
    5. Read the runtime, the usable energy and the recharge time.

    The formula

    t=C20(C2020I)k−1DoD fT faIt = \frac{C_{20}\left(\frac{C_{20}}{20I}\right)^{k-1}\mathrm{DoD}\,f_T\,f_a}{I}

    Reference: Peukert's equation (1897); depth, temperature and age derating follow IEEE 485 battery-sizing practice.

    Worked example

    100 Ah at 12 V running a 500 W load

    Inputs
    • 100 Ah battery at 12 V, 500 W load.
    • 90% inverter efficiency, 80% depth of discharge.
    • Peukert exponent 1.2, new battery at room temperature.
    Calculation path
    1. 1

      The inverter draws 500 / 0.9 = 556 W from the battery, which at 12 V is 46.3 A.

    2. 2

      The twenty-hour current is 5 A, so the discharge is 9.3 times the rated rate.

    3. 3

      Peukert gives 100 × (5 / 46.3)^0.2 = 64.1 Ah of usable capacity at that rate — 36% below the nameplate.

    4. 4

      At 80% depth of discharge that is 51.3 Ah, or 615 Wh.

    5. 5

      Runtime is 51.3 / 46.3 = 1.11 hours, about 67 minutes.

    6. 6

      Recharging at 20 A takes 5 hours, including the absorption taper.

    Result

    1.11 h · 64.1 Ah effective · 615 Wh usable · 5 h to recharge.

    Interpreting the result

    The gap between 100 Ah and 64.1 Ah is the whole point. A runtime estimate that divides nameplate capacity by current gives 1.73 hours here — 56% longer than the battery will actually deliver. Lead-acid is worse than lithium because its Peukert exponent is higher, which is why a lithium pack's runtime tracks the simple arithmetic so much more closely.

    Assumptions & limitations

    • Capacity is rated at the twenty-hour rate, which is the standard for lead-acid.
    • The Peukert exponent is constant over the discharge range; 1.15–1.3 for flooded lead-acid, about 1.1 for AGM, 1.02–1.05 for lithium.
    • The load is constant and the inverter efficiency is constant; both vary in practice.
    • Depth of discharge, temperature and age derating multiply.
    • Recharge assumes 1.25 times the removed charge at a constant current.
    • Self-discharge and the battery's internal resistance rise at end of life are not modelled separately.

    Frequently asked questions

    What is the Peukert exponent?

    A number that describes how much capacity falls as the discharge current rises. A value of 1.0 means no effect; 1.2 means a heavy load gets about 60% of the rated capacity. Lead-acid is 1.15–1.3, AGM about 1.1, lithium close to 1.0.

    How much does cold weather cost me?

    About 1% of capacity per degree below 25 °C for lead-acid, so a battery at 0 °C delivers roughly 75–80% of its rating. Lithium is far less sensitive but cannot be charged below freezing without damage.

    How long should a UPS last?

    Long enough to ride through the outage or to shut down cleanly — usually 5–15 minutes. Sizing for hours is a generator's job, not a battery's, and a battery sized for hours is expensive to replace every few years.

    Why does depth of discharge matter?

    Because the runtime is linear in it, but the cycle life is not. A lead-acid battery cycled to 50% lasts several times longer than one cycled to 80%. The usual compromise is 50% for daily cycling and 80% for standby use.

    Is the inverter efficiency constant?

    No. It peaks at perhaps 30–60% of rated load and falls away at very light loads, where standby consumption dominates. Using the nameplate efficiency is optimistic for a small load and pessimistic for a large one.