Building Energy Estimate
Annual heating and cooling energy from the degree-day method: envelope conductance times degree-days, adjusted for internal gains, divided by plant efficiency. It is the quick estimate an engineer runs before a full hourly model, not a substitute for one.
| HDD | Heating (kWh) | Total cost ($) |
|---|---|---|
| 1000 | 2.720e+4 | 5563 |
| 1500 | 4.080e+4 | 7739 |
| 2000 | 5.440e+4 | 9915 |
| 2500 | 6.800e+4 | 1.209e+4 |
| 3000 | 8.160e+4 | 1.427e+4 |
| 4000 | 1.088e+5 | 1.862e+4 |
A degree-day estimate ignores part-load performance and solar gains.
UA·HDD·24 / (1000·η) × (1 − gains) · Degree-day method.
UA·CDD·24 / (1000·COP) × (1 + gains) · Internal gains raise the cooling load.
annual kWh / floor area · Compare with the benchmark for the building type.
A clear path from inputs to results.
Annual heating and cooling energy from the degree-day method: envelope conductance times degree-days, adjusted for internal gains, divided by plant efficiency. It is the quick estimate an engineer runs before a full hourly model, not a substitute for one.
How to use
- Set floor area (m²).
- Set envelope ua (w/k).
- Set heating degree-days (k·day).
- Set cooling degree-days (k·day).
- Read the headline metrics, then check the table for the detail.
The formula
Reference: ASHRAE Fundamentals, degree-day method.
Worked example
At the default inputs
- Floor area (m²): 1000; Envelope UA (W/K): 1200; Heating degree-days (K·day): 2500; Cooling degree-days (K·day): 800; Internal-gain offset (%): 15; Heating efficiency (%): 90; Cooling COP: 3.5; Energy price ($/kWh): 0.16
- 1
Envelope loss → 7.200e+4 Plant efficiency → 6.800e+4 Cost → $12,091
Annual energy: 7.557e+4 kWh · Heating: 6.800e+4 kWh · Cooling: 7570 kWh
Interpreting the result
The envelope loses about 6.800e+4 kWh of heating energy and needs 7570 kWh of cooling, for 76 kWh/m²·yr and $12,091 a year.
Assumptions & limitations
- One zone with constant UA.
- Plant efficiency and COP are constant.
- Internal gains are a fixed percentage offset.
Frequently asked questions
Is this an hourly model?
No. It is a degree-day estimate; a full model needs bin or hourly weather data.
Why does UA matter more than floor area?
Envelope loss scales with UA, not floor area.
Methodology last reviewed 2026-10-23. Results are informational and not financial or engineering advice — see our disclaimer.