    Heat transfer / convection

    Convection coefficient

    Three geometries cover most of what an engineer needs: forced flow over a flat plate, forced flow inside a pipe, and free convection from a vertical surface. In each case the Nusselt number is a correlation in Reynolds or Rayleigh and Prandtl, and the coefficient is Nu·k/L — so the characteristic length is as important as the correlation itself.

    RegimeMixedFluidAirNu660
    Coefficient h
    17.4 W/m²·K
    660 Nusselt
    Heat flux
    347 W/m²
    at ΔT 20 K
    Reynolds
    6.29e+5
    Mixed
    Rayleigh
    —
    forced convection
    The correlation, step by step
    The Nusselt number is what the correlation gives; the coefficient is Nu·k/L.
    17 W/m²·K
    The correlation, step by step
    QuantityValueNote
    GeometryFlat platecharacteristic length L
    Characteristic length1.000 mlength or height
    Velocity10.00 m/sfree stream
    Reynolds6.293e+5V L / ν
    Grashof—g β ΔT L³ / ν²
    Rayleigh—Gr × Pr
    Prandtl0.707fluid property
    Conductivity0.0263 W/m·Kfluid property
    Nusselt659.9from the correlation
    Coefficient h17.4 W/m²·KNu k / L
    Heat flux347 W/m²h ΔT at 20 K

    Reynolds is 6.29e+5, in the mixed regime. The coefficient scales with velocity^0.8, so doubling the flow does not double the heat transfer.

    Inspect the model
    Choose a quick result view, a scaled comparison, or the complete diagnostic set.
    Coefficient against velocity
    Laminar scales with V^0.5, turbulent with V^0.8 — so doubling the flow never doubles the heat transfer.
    Coefficient against velocity0.00010.1620.3130.4740.6350.781 m/s1 m/s2 m/s2 m/s5 m/s5 m/s10 m/s10 m/s20 m/s20 m/sh
    Three geometries
    The same fluid and length can differ by two orders of magnitude between natural and forced convection.
    Three geometries0.0005.4110.8316.2421.6527.0717.36PlatePlate22.94PipePipe3.22NaturalNaturalh
    Canonical equations
    The exact relationships implemented by this engine.

    Nu = 0.664 Re^0.5 Pr^1/3 · Re below 5 × 10⁵.

    Nu = 0.037 Re^0.8 Pr^1/3 · Above 5 × 10⁵.

    Nu = 0.023 Re^0.8 Pr^n · n = 0.4 heating, 0.3 cooling.

    Nu = 0.59 Ra^0.25 (laminar) · 0.1 Ra^1/3 when turbulent.

    engineering methodology

    A clear path from inputs to results.

    Three geometries cover most of what an engineer needs: forced flow over a flat plate, forced flow inside a pipe, and free convection from a vertical surface. In each case the Nusselt number is a correlation, and the coefficient is Nu·k/L.

    Step-by-step methodWorked exampleAssumptions explained

    How to use

    1. Choose the geometry and the fluid.
    2. Enter the characteristic length and the velocity.
    3. Set the temperature difference and the heat-flow direction.
    4. Read the Nusselt number and the coefficient.

    The formula

    h=Nu kLh = \frac{Nu \, k}{L}

    Reference: Blasius and Colburn for the plate, Dittus-Boelter for the pipe, Churchill-Chu for the vertical plate.

    Worked example

    Air at 10 m/s over a 1 m plate

    Inputs
    • 1 m plate, 10 m/s air at 300 K.
    • ΔT 20 K, heating.
    Calculation path
    1. 1

      The Reynolds number is 10 × 1 / 1.589 × 10⁻⁵ = 6.29 × 10⁵.

    2. 2

      That is in the mixed regime, so Nu = (0.037 Re^0.8 − 871) Pr^1/3 = 658.

    3. 3

      The coefficient is 658 × 0.0263 / 1 = 17.3 W/m²·K.

    4. 4

      At ΔT = 20 K the heat flux is 346 W/m².

    5. 5

      Doubling the velocity to 20 m/s raises h to about 29 W/m²·K — an increase of 68%, not 100%.

    Result

    Nu 658 · 17.3 W/m²·K · 346 W/m².

    Interpreting the result

    The exponent is the practical point: laminar flow scales as V^0.5 and turbulent as V^0.8, so doubling the flow never doubles the heat transfer. That is why a bigger fan has diminishing returns and why the transition to turbulence matters more than the fan setting.

    Assumptions & limitations

    • Fluid properties at 300 K, which is a film-temperature approximation.
    • Smooth surfaces and an unheated starting length of zero.
    • Fully developed flow in the pipe.
    • No boiling, condensation or large property variation.

    Frequently asked questions

    Why is the coefficient lower on a longer plate?

    Because the boundary layer thickens along the plate, so the average coefficient falls with length. That is why a small heat sink outperforms a large flat one per unit area.

    When does natural convection matter?

    When there is no forced flow, or when it is very slow. At 20 K of ΔT on a 1 m vertical surface in air the coefficient is about 3 W/m²·K — an order of magnitude below forced convection.

    What about a fin?

    A fin uses the same coefficient but with an efficiency factor that accounts for the temperature gradient along it. The coefficient is the input, not the answer.

    What is the characteristic length?

    For a plate, the length along the flow; for a pipe, the bore; for a vertical surface, the height. Getting it wrong is the most common error.

    Does the pipe correlation work for gases?

    Yes, Dittus-Boelter is valid for 0.7 < Pr < 160 and Re > 10,000, which covers both air and water. Below Re = 2,300 the flow is laminar and Nu is 3.66.