Duct sizing calculator
Duct sizing is a trade: a smaller duct saves space but raises velocity and fan energy. This calculator finds the circular diameter for a target velocity, computes the Darcy friction factor and the pressure gradient per metre, and shows how steeply the gradient rises as you push the velocity up.
| Term | Value |
|---|---|
| Airflow | 1.000 m³/s (3600 m³/h) |
| Velocity | 5.0 m/s |
| Cross-section | 0.2000 m² |
| Diameter | 505 mm |
| Pressure gradient | 0.54 Pa/m |
| Total over run | 16 Pa |
Round duct. Rectangular equivalents use the same area with a hydraulic-diameter correction.
A = Q / v · Flow divided by velocity.
D = √(4A/π) · Circular equivalent.
Δp = f (L/D) (ρv²/2) · Darcy–Weisbach; f from Swamee-Jain.
A clear path from inputs to results.
Duct sizing is a trade: a smaller duct saves space but raises velocity and fan energy. This calculator finds the circular diameter for a target velocity, computes the Darcy friction factor and the pressure gradient per metre, and shows how steeply the gradient rises as you push the velocity up.
How to use
- Enter the airflow.
- Set the target velocity.
- Enter the run length and duct roughness.
- Read the diameter and the pressure drop.
The formula
Reference: Darcy–Weisbach with the Swamee-Jain approximation to Colebrook–White.
Worked example
1 m³/s at 5 m/s
- Airflow 1 m³/s.
- Velocity 5 m/s.
- Roughness 0.15 mm.
- 1
Area: 1 / 5 = 0.2 m².
- 2
Diameter: √(4 × 0.2/π) = 0.505 m, or 505 mm.
- 3
Velocity pressure: 0.5 × 1.2 × 25 = 15 Pa.
- 4
Friction factor about 0.016, giving roughly 1.2 Pa/m.
505 mm duct · about 1.2 Pa/m.
Interpreting the result
Doubling the velocity halves the area but roughly quadruples the pressure gradient, so fan power climbs with the cube of velocity. Most low-velocity systems stay at 4–6 m/s in mains for that reason.
Assumptions & limitations
- Straight circular duct.
- Standard air at 1.2 kg/m³.
- No fittings, dampers or terminal losses.
- Rigid duct; flexible duct has a higher roughness.
Frequently asked questions
What velocity should I use?
4–6 m/s in mains, 2–3 m/s in branches near occupied space for noise.
Does this include fitting losses?
No. Add local loss coefficients for elbows, tees and terminals.