Motor Starting Voltage Dip
The voltage dip when a large motor starts, from the starting kVA against the available fault level. Utilities and plants both have limits, and a dip beyond about 15% makes contactors chatter.
| Fault level (MVA) | Dip |
|---|---|
| 5 | 27.3% |
| 10 | 15.8% |
| 20 | 8.6% |
| 50 | 3.6% |
| 100 | 1.8% |
ΔV ≈ S_start/(S_fault + S_start) · Per-unit voltage drop.
√3·V·I_start · At the motor terminals.
A clear path from inputs to results.
The voltage dip when a large motor starts, from the starting kVA against the available fault level. Utilities and plants both have limits, and a dip beyond about 15% makes contactors chatter.
How to use
- Set motor rating (kw).
- Set starting current (× flc).
- Set fault level at the terminals (mva).
- Set motor efficiency (%).
- Read the headline metrics, then check the table for the detail.
The formula
Reference: IEEE 399 (Brown Book) motor-starting voltage dip: dip ≈ kVA_start / (kVA_fault + kVA_start), with NEMA MG 1 locked-rotor current.
Worked example
At the default inputs
- Motor rating (kW): 250; Starting current (× FLC): 6; Fault level at the terminals (MVA): 20; Motor efficiency (%): 94; Power factor at start: 0.35
- 1
Voltage dip: 8.6% · Starting kVA: 1877 kVA · Fault level: 20 MVA · Verdict: Acceptable
Voltage dip: 8.6% · Starting kVA: 1877 kVA · Fault level: 20 MVA
Interpreting the result
A 250 kW motor drawing 6.0× FLC dips the terminals 8.6% on a 20 MVA supply.
Assumptions & limitations
- Radial supply, single motor starting.
- No soft starter or VFD.
Frequently asked questions
What dip is acceptable?
About 15% at the motor terminals; less on a sensitive bus.
Does a VFD help?
Yes — it limits the starting current to about the running current.