    HVAC / psychrometrics

    Psychrometric state point

    Moist air is fixed by two independent properties, and every other number on the chart follows. Enter dry bulb with relative humidity, wet bulb or humidity ratio, and this returns the dew point, enthalpy, specific volume and density the coil and duct calculations actually need.

    Relative humidity50.0%Specific volume0.854 m³/kgMoist-air density1.181 kg/m³
    Humidity ratio
    9.30 g/kg
    0.00930 kg per kg of dry air
    Enthalpy
    47.81 kJ/kg
    dry air plus 23.67 kJ of moisture
    Dew point
    12.95 °C
    11.1 K of superheat above saturation
    Wet bulb
    17.07 °C
    depression 6.93 K
    The full state point
    One dry-bulb temperature and one moisture measurement fix every other property.
    24.0 °C
    The full state point
    PropertyValueNote
    Dry-bulb temperature24.00 °CThe number a thermometer reads
    Relative humidity50.0%Vapour pressure over saturation pressure
    Humidity ratio9.30 g/kgMass of water per mass of dry air
    Degrees of saturation49.3%Ratio to the saturation humidity ratio
    Vapour pressure1493 PaPartial pressure of the water vapour
    Saturation pressure2985 PaAt the dry-bulb temperature
    Dew point12.95 °CWhere condensation begins on a surface
    Wet-bulb temperature17.07 °CThermodynamic, not the sling reading
    Enthalpy47.81 kJ/kgReference zero at 0 °C, dry air
    Specific volume0.854 m³/kgPer kilogram of dry air
    Density1.181 kg/m³Of the moist mixture
    Superheat11.05 KAbove the dew point
    Saturation humidity ratio18.88 g/kgThe most moisture the air can hold here
    Total pressure101.33 kPaSite barometric pressure

    The dew point is the design number for condensation, not the relative humidity. A surface below it will be wet regardless of how low the RH reads.

    Inspect the model
    Choose a quick result view, a scaled comparison, or the complete diagnostic set.
    State point against the saturation curve
    The gap between the flat line and the curve is how much more moisture the air could still take.
    State point against the saturation curve0.00010.3420.6731.0141.3551.6844779912121515171720202222252528283030333336363939SaturationThis state
    The state point
    Temperature, humidity ratio and wet bulb, each in its own unit.
    The state point0.00011.8023.6035.4047.2059.0024.00Dry bulb °CDry bulb °C17.07Wet bulb °CWet bulb °C12.95Dew point °CDew point °C50.00RH %RH %Value
    Canonical equations
    The exact relationships implemented by this engine.

    W = 0.621945 p_w / (p − p_w) · The 0.621945 is the molecular-weight ratio of water to dry air.

    h = 1.006 T + W(2501 + 1.86 T) · kJ per kg of dry air, T in °C.

    ln p_ws = C₈/T + C₉ + C₁₀T + C₁₁T² + C₁₂T³ + C₁₃ ln T · ASHRAE eq. 6 over water; a separate fit over ice.

    W = ((2501 − 2.326 T_wb) W_s* − 1.006(T − T_wb)) / (2501 + 1.86 T − 4.186 T_wb) · Solved by bisection on T_wb.

    engineering methodology

    A clear path from inputs to results.

    Moist air is fixed by two independent properties, and every other number on the psychrometric chart follows from them. Enter dry bulb with relative humidity, wet bulb or humidity ratio, and this returns the dew point, enthalpy, specific volume and density the coil and duct calculations actually need.

    Step-by-step methodWorked exampleAssumptions explained

    How to use

    1. Choose which pair of properties you know.
    2. Enter the dry-bulb temperature and the second property.
    3. Set the site barometric pressure if you are above sea level.
    4. Read the humidity ratio, enthalpy, dew point and wet bulb.
    5. Use the dew point — not the relative humidity — as the condensation threshold.

    The formula

    W=0.621945 pwp−pw  ;  h=1.006 T+W(2501+1.86 T)  ;  ln⁡pws=C8T+C9+C10T+C11T2+C12T3+C13ln⁡TW = \frac{0.621945\,p_w}{p-p_w} \;;\; h = 1.006\,T + W(2501 + 1.86\,T) \;;\; \ln p_{ws} = \frac{C_8}{T}+C_9+C_{10}T+C_{11}T^2+C_{12}T^3+C_{13}\ln T

    Reference: ASHRAE Handbook — Fundamentals 2017, Chapter 1: Equations 5 and 6 (Hyland–Wexler), 20, 32 and 33.

    Worked example

    24 °C at 50% relative humidity

    Inputs
    • Dry-bulb temperature 24 °C.
    • Relative humidity 50%.
    • Sea-level pressure 101.325 kPa.
    Calculation path
    1. 1

      Saturation pressure at 24 °C is 2,985 Pa from the Hyland–Wexler fit.

    2. 2

      Vapour pressure is 50% of that: 1,493 Pa.

    3. 3

      W = 0.621945 × 1,493 / (101,325 − 1,493) = 0.00930 kg/kg, or 9.30 g/kg.

    4. 4

      Enthalpy is 1.006 × 24 + 0.00930 × (2501 + 1.86 × 24) = 47.81 kJ/kg.

    5. 5

      The dew point is the temperature where the saturation pressure equals 1,493 Pa: 12.95 °C.

    6. 6

      The thermodynamic wet bulb, solved from the saturation identity, is 17.07 °C.

    Result

    9.30 g/kg · 47.81 kJ/kg · dew point 12.95 °C · wet bulb 17.07 °C.

    Interpreting the result

    The dew point is the number that matters for condensation: any surface below 12.95 °C will be wet, whatever the relative humidity says. The wet bulb is what evaporative cooling can reach, and the gap between it and the dry bulb — 6.9 K here — is the evaporative cooling potential. The humidity ratio is what the mass and energy balances use, because it is conserved when air is heated or cooled without condensation.

    Assumptions & limitations

    • Saturation pressure uses the ASHRAE Hyland–Wexler formulation over water above 0 °C and the ice fit below it.
    • The pressure is the site barometric pressure; assuming sea level at altitude is a common source of a few percent error in the humidity ratio.
    • The wet bulb is the thermodynamic value, not the reading of a sling psychrometer, which includes a small radiation and ventilation error.
    • Enthalpy uses a reference of zero for dry air at 0 °C and saturated liquid water at 0 °C.
    • Above 100% relative humidity the state is supersaturated; the model clamps rather than reporting a fog.

    Frequently asked questions

    What is the difference between relative humidity and humidity ratio?

    Relative humidity is how full the air is relative to saturation at that temperature, so it changes when you heat or cool the air without adding moisture. Humidity ratio is the actual mass of water per mass of dry air, and it only changes when moisture is added or removed. Energy balances use the ratio.

    Why does altitude change the answer?

    Because the humidity ratio depends on the total pressure in the denominator. At 1,500 m the pressure is about 84 kPa, so the same vapour pressure corresponds to a higher humidity ratio and a higher relative humidity for the same dry bulb.

    What is the wet-bulb depression?

    The dry bulb minus the wet bulb. It is the evaporative cooling available: dry air has a large depression, humid air almost none. At 24 °C and 50% it is 6.9 K, so evaporative cooling can reach about 17 °C at best.

    Why does my dew point calculation differ from an online chart?

    Usually a different saturation-pressure fit. The Magnus approximation used by many simple tools differs from the ASHRAE tabulated values by about 0.4% above freezing, which is a few hundredths of a degree in the dew point. Below 0 °C the difference is larger, because the ice branch matters.

    How do I use this for a cooling coil?

    Read the entering and leaving states, then find where the straight line between them meets saturation — that is the apparatus dew point. The bypass factor is the ratio of the leaving-to-ADP temperature difference over the entering-to-ADP difference.