Optional Method service load
The optional method exists because the standard method double-counts: it charges the lighting, the receptacles, the appliances and the HVAC separately and adds them, when a house never draws all of it at once. §220.82 takes 100% of the first 10 kVA of the general load and 40% of the rest, then adds the heating or cooling at its own percentage. The result is frequently a smaller service — and occasionally larger, which is why both have to be computed.
| Line | VA | Rule |
|---|---|---|
| General load | 38,000 | lighting, circuits, appliances |
| After 100%/40% | 21,200 | §220.82(B) |
| Heating and cooling | 10,800 | Resistance heat at 100% of 10 kW and 40% above — §220.82(C)(4) |
| Total | 32,000 | general demand plus HVAC |
| Service current | 133.3 A | total ÷ 240 V |
| Optional Method rating | 150 A | next standard size |
| Standard Method rating | 200 A | Article 220 Part III |
| Difference | -50 A | optional is smaller |
The general load of 38,000 VA becomes 21,200 VA after the 100%/40% factor, and resistance heat at 100% of 10 kw and 40% above — §220.82(c)(4) adds 10,800 VA.
min(L, 10k) + 0.4 (L − 10k) · §220.82(B).
100% of nameplate · §220.82(C)(1).
100% compressor + 65% supplemental · §220.82(C)(2).
100% to 10 kW, 40% above · §220.82(C)(4).
A clear path from inputs to results.
The optional method exists because the standard method double-counts: it charges the lighting, the receptacles, the appliances and the HVAC separately and adds them, when a house never draws all of it at once.
How to use
- Enter the floor area and the appliance nameplates.
- Add the air conditioning, heat pump and resistance heat.
- Read the general load and its 100%/40% demand.
- Compare the result with the standard method.
The formula
Reference: NFPA 70 §220.82, optional feeder and service load calculations.
Worked example
A 2,000 ft² house with electric resistance heat
- 2,000 ft², two small-appliance circuits, laundry.
- 12 kW range, 5 kW dryer, 4.5 kW water heater, 6 kW other appliances.
- 6 kW air conditioning, 12 kW resistance heat.
- 1
The general load is 6,000 + 3,000 + 1,500 + 12,000 + 5,000 + 4,500 + 6,000 = 38,000 VA.
- 2
Under §220.82(B) that becomes 10,000 + 0.4 × 28,000 = 21,200 VA.
- 3
Resistance heat at 12 kW takes 100% of the first 10 kW and 40% of the rest, or 10,800 VA — larger than the air conditioning at 6,000 VA.
- 4
The total is 32,000 VA, which is 133 A at 240 V.
- 5
The standard method on the same house gives 183.5 A, so the optional method saves a service size.
32,000 VA · 133 A · 150 A service.
Interpreting the result
The two methods can disagree in either direction. On a large house with a big connected load the optional method almost always wins; on a small house with electric resistance heat the HVAC clause can make it larger than the standard method, which is why the code allows either rather than requiring one.
Assumptions & limitations
- A one-family dwelling with a service of 100 A or more.
- General lighting at 3 VA/ft².
- The §220.82(C) clauses are alternatives, not additive.
- No largest-motor adder or EV charging.
Frequently asked questions
Which method should I use?
Either — the code permits both. Compute both and use the smaller, but the optional method is only available for a dwelling with a 100 A or more service.
What counts as the general load?
Lighting, the small-appliance and laundry circuits, and the nameplate rating of every appliance fastened in place — range, dryer, water heater, disposer, dishwasher and so on.
Can I use it for a multifamily building?
§220.84 covers multifamily dwellings with a different set of factors. The single-dwelling optional method does not apply.
Why is the HVAC clause not additive?
Because heating and cooling never run together. The code takes the largest single clause, which for a heat pump is the compressor at 100% plus 65% of the supplemental resistance.
Does the 100 A floor ever bind?
On a small house with gas heat and no large appliances, yes. The calculation can come out below 100 A and the service still has to be 100 A.
Methodology last reviewed 2026-10-22. Results are informational and not financial or engineering advice — see our disclaimer.