Short-circuit calculator
The fault level at the end of a cable run, built from the transformer impedance and the cable impedance, with the peak current from the X/R ratio and the adiabatic cable size for the clearing time. Change the cable length and watch the fault level fall.
| Element | R (mΩ) | X (mΩ) | Z (mΩ) |
|---|---|---|---|
| Transformer | 0.96 | 9.55 | 9.60 |
| Cable | 4.80 | 2.40 | 5.37 |
| Total | 5.76 | 11.95 | 13.27 |
Cable impedance grows with length; a long run can halve the fault level and change the breaker rating.
I″k = c·Un / (√3·Zk) · IEC 60909, radial single source.
Zt = uk · Un² / Sn · uk as a fraction, Un in kV, Sn in MVA.
ip = κ·√2·I″k · κ from the X/R ratio at the fault point.
A clear path from inputs to results.
The prospective fault current decides the breaker rating, the cable damage check and the arc flash study. It is set by the transformer impedance and the cable run, and it falls quickly with distance — which is why the point of fault matters.
How to use
- Enter the transformer rating, impedance and X/R ratio.
- Set the cable length and its resistance and reactance per kilometre.
- Read the fault current, the peak current and the minimum adiabatic cable size.
The formula
Reference: IEC 60909-0 radial network; adiabatic check from IEC 60364-5-54.
Worked example
1 MVA transformer, 400 V, 30 m of cable
- uk 6%, X/R 10, cable 0.16 + j0.08 Ω/km.
- 1
Zt = 0.06 × 0.4²/1 = 9.6 mΩ. Cable adds 4.8 + j2.4 mΩ. Zk = 14.4 mΩ. I″k = 1.05 × 400/(√3 × 0.0144) = 16.8 kA.
16.8 kA at the far end, 25.3 kA at the terminals.
Interpreting the result
A long run can halve the fault level, which is good for the breaker rating and bad for the disconnection time — the same cable that protects the equipment may not trip the breaker at the far end.
Assumptions & limitations
- Radial, single source; no motor contribution.
- Utility impedance is neglected, which raises the fault level.
- Cable resistance at operating temperature.
- Arc resistance is not included.
Frequently asked questions
Why does c = 1.05?
IEC 60909 uses a voltage factor to cover tolerance: 1.05 for low voltage, 1.10 for high voltage.
What is the adiabatic check?
It sizes the conductor so the fault energy I²t does not take it above its short-time temperature limit.
Should I use the maximum or minimum fault?
Maximum for equipment rating, minimum for protection disconnection. This is the maximum.
Does the X/R ratio matter?
It sets the peak, which is what a busbar and a breaker’s making capacity see.
Methodology last reviewed 2026-10-22. Results are informational and not financial or engineering advice — see our disclaimer.