    Solar PV / system sizing

    Solar panel sizing

    Size a PV array from a daily energy demand, then get the panel count, battery bank and simple payback. System losses are applied before sizing, which is what separates a real design from a nameplate calculation.

    Performance ratio82%CO₂ avoided2.0 t/yrAnnual saving$760.27
    Array size
    3.78 kW
    9 × 420 W panels
    Annual yield
    4752 kWh
    13.0 kWh/day average
    Battery bank
    22.5 kWh
    1.5 days autonomy
    Simple payback
    4.2 yr
    Against $3,213 installed cost
    Array and storage sizing
    The energy balance from daily demand through to panel count, battery bank and payback.
    9 panels
    Array and storage sizing
    ItemValueBasis
    Daily demand12.00 kWhEntered
    Peak sun hours4.20 hSite-specific, worst-month or annual average
    System losses18.0%Inverter, wiring, soiling, temperature
    Required array3.484 kWE/(PSH × (1 − losses))
    Panel rating420 WNameplate at STC
    Panels needed9Rounded up to whole modules
    Installed capacity3.780 kW9 × 420 W
    Annual yield4752 kWh13.02 kWh/day average
    Battery bank22.50 kWh1.5 days autonomy at 80% DoD
    Installed cost$3,213$0.85 per watt
    Simple payback4.2 yrAt $0.16/kWh

    Sizing on the annual average under-builds for winter. Size on the worst-month PSH if the system must be self-sufficient year-round.

    Inspect the model
    Choose a quick result view, a scaled comparison, or the complete diagnostic set.
    Monthly yield
    Seasonal variation around the annual average.
    Monthly yield0.000123.62247.23370.85494.46618.08JanJanFebFebMarMarAprAprMayMayJunJunJulJulAugAugSepSepOctOctNovNovDecDeckWh
    Array size vs peak sun hours
    Better insolation needs proportionally less installed capacity for the same demand.
    Array size vs peak sun hours0.0001.693.395.086.778.472 h2 h3 h3 h4 h4 h5 h5 h6 h6 h7 h7 hRequired kWInstalled kW
    Canonical equations
    The exact relationships implemented by this engine.

    P = E_daily/(PSH·(1−losses)) · energy balance over one day

    N = ⌈P·1000/P_panel⌉ · rounded up to whole modules

    C = E_daily·autonomy/DoD · depth of discharge derating

    E_year = P·PSH·365·(1−losses) · annual energy production

    engineering methodology

    A clear path from inputs to results.

    Solar sizing is an energy balance, not a wattage guess. Daily demand divided by effective sun hours gives the array; autonomy divided by depth of discharge gives the battery. The derate factor is where most optimistic designs go wrong, so it is applied before the array size is calculated.

    Step-by-step methodWorked exampleAssumptions explained

    How to use

    1. Enter the daily energy demand in kilowatt-hours. Use a real bill, not an estimate.
    2. Set the peak sun hours for the site — the worst month if the system must be self-sufficient.
    3. Apply a system loss factor: inverter, wiring, soiling and temperature together are typically 15–25%.
    4. Choose the panel rating.
    5. Set battery autonomy days and depth of discharge. Use zero autonomy for a grid-tied system.
    6. Read the panel count, annual yield and simple payback.

    The formula

    Parray=EdailyPSH (1−ηloss),N=⌈Parray⋅1000Ppanel⌉,Cbatt=Edaily⋅autonomyDoDP_{\text{array}} = \frac{E_{\text{daily}}}{\mathrm{PSH}\,(1-\eta_{\text{loss}})}, \qquad N = \left\lceil \frac{P_{\text{array}}\cdot 1000}{P_{\text{panel}}} \right\rceil, \qquad C_{\text{batt}} = \frac{E_{\text{daily}}\cdot \text{autonomy}}{\mathrm{DoD}}

    Reference: IEC 62548 (PV array design); NREL PVWatts derate conventions.

    Worked example

    12 kWh/day at 4.2 peak sun hours (default inputs)

    Inputs
    • Daily demand 12 kWh.
    • Peak sun hours 4.2.
    • System losses 18%.
    • Panels 420 W.
    • Autonomy 1.5 days at 80% depth of discharge.
    Calculation path
    1. 1

      Effective sun hours: 4.2 × 0.82 = 3.444.

    2. 2

      Required array: 12 / 3.444 = 3.484 kW.

    3. 3

      Panels: ⌈3,484 / 420⌉ = 9 panels, giving 3.78 kW installed.

    4. 4

      Annual yield: 3.78 × 4.2 × 365 × 0.82 = 4,752 kWh.

    5. 5

      Battery: 12 × 1.5 / 0.80 = 22.5 kWh of nominal capacity.

    Result

    3.48 kW required · 9 panels (3.78 kW installed) · 4,752 kWh a year · 22.5 kWh battery.

    Interpreting the result

    The 18% derate turns a 3.48 kW requirement into 3.78 kW of installed panels — a 9% oversize that is not waste but physics. Annual yield of 4,752 kWh against a 4,380 kWh demand leaves a small surplus, which is the right side to err on. The battery is the expensive part: 22.5 kWh of nominal capacity at 80% DoD delivers 18 kWh usable, covering one and a half days.

    Assumptions & limitations

    • Peak sun hours are an annual or worst-month average, not a peak instantaneous value.
    • Losses are lumped into one derate. A detailed design separates inverter, wiring, soiling, mismatch and temperature coefficients.
    • Panels face the optimal direction at the optimal tilt with no shading.
    • Battery round-trip efficiency is folded into the depth-of-discharge figure; in practice it is a separate 5–10% loss.
    • No degradation over time; panels lose about 0.5% of output a year.

    Frequently asked questions

    What are peak sun hours?

    The number of hours per day at an irradiance of 1,000 W/m² that would deliver the same total energy as the actual varying sun. It is an energy measure, not a count of daylight hours.

    How do I size for winter?

    Use the worst-month peak sun hours rather than the annual average. In northern latitudes that can be half the summer value, which roughly doubles the array.

    Is the payback calculation realistic?

    It is a simple payback with no discounting, no degradation and no maintenance. Treat it as an order-of-magnitude figure; a full model would use levelised cost of energy.

    Why apply losses before sizing?

    Because the array must produce the demand after losses, not before. Sizing on nameplate output under-builds by the derate factor, which is how systems end up 20% short in winter.

    What depth of discharge should I use?

    80% for lithium iron phosphate, 50% for lead-acid if you want reasonable cycle life. Deeper discharge shortens battery life, so the nominal capacity must be larger.

    Do I need a battery for a grid-tied system?

    No. A grid-tied system without storage exports surplus and draws at night, and is considerably cheaper. Batteries are for autonomy, not for saving money in most markets.

    Methodology last reviewed 2026-10-18. Results are informational and not financial or engineering advice — see our disclaimer.