    Electrical / boxes

    Box fill

    Conduit fill asks how much a raceway will hold; box fill asks whether there is room to make the joints. The rule is a volume budget — every conductor, every clamp, every device and one allowance for all the equipment grounds together consumes cubic inches, and the box has to have enough of them.

    VerdictPassesPer conductor2.25 in³Box4 × 4 × 2⅛
    Required volume
    20.25 in³
    box has 30.3 in³
    Spare
    10.05 in³
    within the box
    Utilisation
    67%
    passes §314.16
    Conductors it holds
    13
    at 12 AWG
    The volume budget
    Every item consumes a multiple of one conductor allowance; the grounds share a single one.
    20.25 in³
    The volume budget
    ItemCountVolume
    Ungrounded conductors36.75 in³
    Grounded conductors24.50 in³
    Equipment grounds (one allowance)12.25 in³
    Devices (two allowances each)14.50 in³
    Clamps12.25 in³
    Support fittings00.00 in³
    Luminaire wires00.00 in³
    Total required—20.25 in³
    Box volume—30.30 in³
    Spare—10.05 in³
    Smallest box that passes—4 × 4 × 1½ in square

    §314.16(B)(5) is the rule people miss: all the equipment grounding conductors together take one allowance, not one each. A device takes two allowances, because it displaces conductors on both sides.

    Inspect the model
    Choose a quick result view, a scaled comparison, or the complete diagnostic set.
    Volume allowance by conductor size
    Table 314.16(B): the allowance is per conductor, not per cubic inch of copper.
    Volume allowance by conductor size0.0001.182.363.544.725.902.0014 AWG14 AWG2.2512 AWG12 AWG2.5010 AWG10 AWG3.008 AWG8 AWG5.006 AWG6 AWGin³ each
    Required volume against conductor count
    Linear in the conductor count, with a step at each device and clamp.
    Required volume against conductor count0.0006.5513.1019.6626.2132.762244668810101212Required
    Canonical equations
    The exact relationships implemented by this engine.

    (ungrounded + grounded) × A · One allowance each.

    1 × A · All of them together, §314.16(B)(5).

    devices × 2 × A · §314.16(B)(4).

    Σ ≤ box volume · Table 314.16(A).

    engineering methodology

    A clear path from inputs to results.

    Conduit fill asks how much a raceway will hold; box fill asks whether there is room to make the joints. The rule is a volume budget — every conductor, every clamp, every device and one allowance for all the equipment grounds together consumes cubic inches.

    Step-by-step methodWorked exampleAssumptions explained

    How to use

    1. Choose the box and the conductor size.
    2. Count the ungrounded, grounded and grounding conductors.
    3. Add devices, clamps, fittings and any luminaire wires.
    4. Read the required volume against the box volume.

    The formula

    V=(nu+ng)A+A+2dA+cA+fAV = (n_u + n_g)A + A + 2dA + cA + fA

    Reference: NFPA 70 §314.16, Table 314.16(A) for box volumes and Table 314.16(B) for the conductor allowance.

    Worked example

    Three hots, two neutrals, one ground, one device in a 4×4×2⅛ box

    Inputs
    • 4 × 4 × 2⅛ in square box, 30.3 in³.
    • 12 AWG conductors at 2.25 in³ each.
    • 3 ungrounded, 2 grounded, 1 ground, 1 device, 1 clamp.
    Calculation path
    1. 1

      Five conductors take 5 × 2.25 = 11.25 in³.

    2. 2

      All the equipment grounds together take one allowance, 2.25 in³.

    3. 3

      The device takes two allowances, 4.5 in³, and the clamp one, 2.25 in³.

    4. 4

      The total is 20.25 in³ against 30.3 in³ available.

    5. 5

      The box passes with 10.05 in³ to spare, and would hold 13 conductors of this size.

    Result

    20.25 in³ required · 30.3 in³ available · passes.

    Interpreting the result

    The rule people miss is that all the equipment grounding conductors share one allowance. A box with four grounds is not charged four times; a box with four devices is, because each device displaces conductors on both sides. That is why a two-gang box fills up faster than the conductor count suggests.

    Assumptions & limitations

    • Metal boxes with the Table 314.16(A) volumes.
    • All conductors are the same size; mixed sizes are calculated at the largest allowance.
    • One allowance for all equipment grounding conductors.
    • Boxes with a marked volume may use the marked figure.

    Frequently asked questions

    Why do all the grounds share one allowance?

    Because they are not current-carrying and they terminate together. §314.16(B)(5) gives them a single allowance based on the largest one.

    What about a box with 14 and 12 AWG?

    Every conductor is calculated at the larger allowance, so mixing sizes in a small box runs out of volume quickly.

    What if the box is non-metallic?

    Use the volume marked on the box; the Table 314.16(A) figures apply to metal boxes only.

    Does a receptacle count as two conductors?

    It counts as two allowances, not two conductors — the device occupies space on both sides of the box, so §314.16(B)(4) charges it double.

    Do cable clamps count?

    Yes, one allowance each, unless the clamp is listed as not requiring one — which is marked on the box.