Grounding electrode and equipment conductors
Two tables that look alike and are not. Table 250.66 sizes the grounding electrode conductor from the largest ungrounded service conductor — it is keyed to the service capacity. Table 250.122 sizes the equipment grounding conductor from the overcurrent device — it is keyed to what will clear a fault. Confusing the two is the most common grounding error in a panel schedule.
| Item | Size | Source |
|---|---|---|
| Largest service conductor | 4/0 copper | as entered |
| Table 250.66 | 2 AWG copper | keyed to the service capacity |
| Electrode type | rod | rod, pipe or plate |
| Electrode cap | 6 AWG | §250.66(A) or (B) |
| GEC required | 6 AWG copper | the larger of the table and the cap |
| Largest feeder OCPD | 200 A | as entered |
| Equipment ground | 6 AWG copper | Table 250.122 |
| Aluminium EGC | 4 AWG | Table 250.122 |
Table 250.66 calls for 2, but §250.66(A) caps the requirement at 6 for that electrode, so 6 is the size to run.
Table 250.66(largest service conductor) · Service capacity.
min(table, 6 AWG copper) · §250.66(A).
min(table, 4 AWG copper) · §250.66(B).
Table 250.122(OCPD) · Fault-clearing capacity.
A clear path from inputs to results.
Two tables that look alike and are not. Table 250.66 sizes the grounding electrode conductor from the largest ungrounded service conductor — it is keyed to the service capacity. Table 250.122 sizes the equipment grounding conductor from the overcurrent device — it is keyed to what will clear a fault.
How to use
- Choose the largest service conductor and its material.
- Set the largest feeder breaker rating.
- Pick the electrode type.
- Read the grounding electrode conductor and the equipment ground.
The formula
Reference: NFPA 70 Table 250.66, Table 250.122, §250.66(A) to (C).
Worked example
A 4/0 copper service with a rod electrode
- Largest service conductor 4/0 copper.
- Largest feeder breaker 200 A.
- Rod, pipe or plate electrode.
- 1
Table 250.66 gives 2 AWG copper for a service conductor over 3/0 through 350 kcmil.
- 2
A rod electrode caps the requirement at 6 AWG under §250.66(A).
- 3
So 6 AWG is what is actually run, even though the table asks for 2 AWG.
- 4
The equipment ground for a 200 A device is 6 AWG copper from Table 250.122.
- 5
The two numbers happen to agree here, which is exactly why the confusion persists.
2 AWG from the table · 6 AWG after the cap · 6 AWG equipment ground.
Interpreting the result
The cap exists because a rod cannot use more copper than its surface area can transfer into the earth — a 3/0 conductor to a 5/8 inch rod buys nothing. The equipment ground has no such cap, because its job is different: it has to carry fault current long enough for the breaker to trip.
Assumptions & limitations
- Service conductors are sized per Article 310.
- The electrode is a single rod, pipe, plate, concrete-encased electrode or ground ring.
- The equipment ground is sized from the largest overcurrent device on the feeder.
- The §250.122(B) proportional increase for voltage-drop upsizing is not applied.
Frequently asked questions
Why is the electrode conductor sometimes smaller than the table?
Because §250.66(A) to (C) cap the requirement by electrode type: 6 AWG for a rod, 4 AWG for concrete-encased, 2 AWG for a ground ring. Above that the extra copper does nothing.
Can I use aluminium for the grounding electrode conductor?
Not where it will be in contact with masonry or earth, and never below the sizes in the table. Copper is the default for a reason.
What if the service is upsized for voltage drop?
The equipment ground must be increased proportionally under §250.122(B), which is a separate calculation from the table.
What is the difference between the two tables?
250.66 is keyed to the service capacity and protects the electrode connection. 250.122 is keyed to the breaker and ensures a fault has a low-impedance path back to trip it.
Does a metal water pipe count as an electrode?
Yes, if it is in contact with the earth for 10 feet or more, and it must be supplemented by another electrode under §250.53(D)(2).
Methodology last reviewed 2026-10-22. Results are informational and not financial or engineering advice — see our disclaimer.